Specification for Neutral-supported Secondary and Service Drop Copper Cables, Duplex/Triplex/Quadruplex, 600 volts, 75C





SIZE
PHASE CONDUCTOR
NEUTRAL CONDUCTOR
HARD-DRAWN COPPER
AWG STRAND CONSTRUCTION Copper BARE DIAMETER NOMINAL CONDUCTOR RESISTANCE @ 20oC INSULATION THICKNESS Min. Ave. NO.& DIA. of WIRES BARE DIAMETER
mm mm ohms/km mm mm mm
8 solid 3.264 2.060 1.14 solid 3.264
6 7 x 1.56 4.670 1.320 1.14 7 x 1.56 4.670
4 7 x 1.96 5.880 0.832 1.14 7 x 1.96 5.880
2 7 x 2.47 7.420 0.523 1.14 7 x 2.47 7.420
1 19 x 1.69 8.430 0.415 1.52 19 x 1.69 8.430
1/0 19 x1.89 9.460 0.329 1.52 19 x 1.89 9.460
2/0 19 x 2.13 10.600 0.261 1.52 19 x 2.13 10.600

Note: Insulation material may be Low-density Polyethylene or High-density Polyethylene as per customer's specification

Reference
ICEA S-61-402, NEMA WC5, Thermoplastic-insulated Wire and Cable for the Transmission and Distribution of Electrical Energy