Specification for Neutral-supported Secondary and Service Drop Copper
Cables, Duplex/Triplex/Quadruplex, 600 volts, 75C
|
SIZE
|
PHASE
CONDUCTOR
|
NEUTRAL
CONDUCTOR
HARD-DRAWN COPPER
|
| AWG |
STRAND
CONSTRUCTION Copper |
BARE
DIAMETER |
NOMINAL
CONDUCTOR RESISTANCE @ 20oC |
INSULATION
THICKNESS Min. Ave. |
NO.&
DIA. of WIRES |
BARE
DIAMETER |
|
mm |
mm |
ohms/km |
mm |
mm |
mm |
| 8 |
solid |
3.264 |
2.060 |
1.14 |
solid |
3.264 |
| 6 |
7
x 1.56 |
4.670 |
1.320 |
1.14 |
7
x 1.56 |
4.670 |
| 4 |
7
x 1.96 |
5.880 |
0.832 |
1.14 |
7
x 1.96 |
5.880 |
| 2 |
7
x 2.47 |
7.420 |
0.523 |
1.14 |
7
x 2.47 |
7.420 |
| 1 |
19
x 1.69 |
8.430 |
0.415 |
1.52 |
19
x 1.69 |
8.430 |
| 1/0 |
19
x1.89 |
9.460 |
0.329 |
1.52 |
19
x 1.89 |
9.460 |
| 2/0 |
19
x 2.13 |
10.600 |
0.261 |
1.52 |
19
x 2.13 |
10.600 |
Note:
Insulation material may be Low-density Polyethylene or High-density
Polyethylene as per customer's specification
Reference
ICEA S-61-402, NEMA WC5, Thermoplastic-insulated Wire and Cable for
the Transmission and Distribution of Electrical Energy
|
    
|
 |