Specification for PE-Insulated All Aluminum Conductor (Poly AAC)
| SIZE |
CODE
NAME |
PHASE
CONDUCTOR |
ACSR
NEUTRAL CONDUCTOR |
| AWG |
STRAND
CONSTRUCTION |
BARE
DIAMETER |
INSULATION
THICKNESS |
STRAND
CONSTRUCTION |
DIAMETER |
| |
|
Aluminum |
|
Min.
Ave. |
Aluminum |
Steel |
|
| . |
. |
mm |
mm |
mm |
mm |
mm |
mm |
| 6 |
SHEPHERD |
7
x 1.560 |
4.680 |
1.14 |
6
x 1.679 |
1
x 1.679 |
5.037 |
| 4 |
TERRIER |
7
x 1.960 |
5.880 |
1.14 |
6
x 2.118 |
1
x 2.118 |
6.354 |
| 2 |
CHOW |
7
x 2.474 |
7.422 |
1.14 |
6
x 2.672 |
1
x 2.672 |
8.016 |
| 1/0 |
BLOODHOUND |
7
x 3.119 |
9.357 |
1.52 |
6
x 3.371 |
1
x 3.371 |
10.113 |
| 2/0 |
|
7
x 3.503 |
10.516 |
1.52 |
6
x 3.785 |
1
x 3.785 |
11.355 |
| 3/0 |
|
7
x 3.932 |
11.786 |
1.52 |
6
x 4.250 |
1
x 4.250 |
12.750 |
| 4/0 |
|
7
x 4.417 |
13.260 |
1.52 |
6
x 4.770 |
1
x 4.770 |
14.310 |
Note:
Insulation material may be Low-density Polyethylene or High-density
Polyethylene as per customer's specification
Reference
ICEA S-61-402, NEMA WC5, Thermoplastic-insulated Wire and Cable for
the Transmission and Distribution of Electrical Energy
|
    
|
 |